Generator Step-Up Transformers

Efficient Long-Distance Power Distribution

GSU transformers are used worldwide to raise voltages coming from power generation plants, including thermal, nuclear, and hydroelectric. Typical configurations require a Delta connected LV winding to induced currents in the Generator and Wye connected HV windings to connect to the transmission lines.

Prolec® GE and Waukesha® GSUs are engineered and manufactured to uphold the highest standards of reliability. By adhering to stringent quality control measures and utilizing top-grade materials and components, these transformers consistently exceed the expectations of our customers.

Prolec GE GSU

These transformers are manufactured in our Mexico, United States and Brazil facilities.

 

Download brochure

Standard GSU

GSU is a transformer directly connected to a generator. Generators are designed to produce constant voltage between 13 kV and 25 kV. These transformers then step up the voltage from the generator to match the transmission system.

Typical Ratings
  • Low voltage: 13.2 kV through 25 kV – delta connection
  • High voltage: 69 kV through 765 kV – wye connection
Plant Capabilities
  • Up to 600 MVA single phase and 900 MVA three phase, up to 1000 MVA (Brazil facility)
  • Up to 550kV (North American facilities), 800kV (Brazil facility) high voltage
Common Characteristics
  • LTC will be on high voltage side (if required)
  • Overload conditions are not required
  • Sound requirements per NEMA TR1
  • Large units with heat exchangers and pumps (OFAF, ODAF)
  • Single phase banks (4 units total, 3+1 spare)
  • LV bushings typically have isolated phase bus duct (high temp bushing)

Station Service

SSTs serve as backup power to a power plant and are fed from the grid.

Typical Ratings
  • Under 50 MVA top rated
  • High Voltage: 69 kV and above – delta or wye connection
  • Low Voltage: 6 to 16 kV – typically wye connection
Plant Capabilities
  • Up to 600 MVA single phase and 900 MVA three phase
  • Up to 550kV high voltage
  • Single or dual secondary windings (XV and YV, HV MVA equals XV MVA + YV MVA)
Common Characteristics
  • Side mounted bushings common (LV typically)
  • Air terminal chambers common
  • LV neutral grounded through neutral grounding resistor (NGR)

Unit Auxiliary

UATs get power from a generator within a generation facility through the HV windings and distribute power to the plant through the XV windings. Since a generator will produce voltages unfavorable to facility operation, a transformer is needed to supply appropriate voltages.

Typical Ratings
  • Under 50 MVA top rated
  • Typically 8 kV, 18 kV and 21kV (typical generator voltages), stepping down from 6 to 4.16 kV (IEEE has suggested voltages) – delta – wye connection
Plant Capabilities
  • Under 50 MVA top rated due to testing limits
  • Up to 550kV high voltage
  • Single or dual secondary windings (XV and YV, HV MVA equals XV MVA + YV MVA)
Common Characteristics
  • Side mounted bushings common (LV typically)
  • HV bushings typically have isolated phase bus duct (high temp bushing)
  • Air terminal chambers common
  • LV neutral grounded through neutral grounding resistor (NGR)
  • Connected directly to generator

Prolec GE Monterrey

Prolec GE Brazil

Prolec GE Waukesha